Skip to content

General Purpose Analog I/O Configuration

The following methods are recommended for high reliability.

  • Use analog GND closest to I/O.
  • Equipment and control box use the same GND. Analog I/O is not isolated from the robot control box.
  • Use shielded or twisted-pair cable. Connect to the GND shield on the Power (J12) terminal.
TerminalParameterMinTypeMaxUnit
Voltage mode Input
AIx - AGVoltage0-10V
AIx - AGResolution-16-Bit
Voltage mode Output
AOx – AGVoltage0-10V
AOx – AGResolution-16-Bit

1. Analog output

The analog output can be used to control speed of conveyor. The figure below illustrates a simple demonstration.

missing

2. Analog input

The output value of the analog sensor can be used by the control box as analog input. The figure shown below illustrates a simple connection to an analog sensor.

missing

3. LCD Status Display

missing

  1. Display Box(1): Displays information about system status.
    • Please Wait: The main PC in the control box is booting up.
    • default: The main PC in the control box is ready.
  2. Display Box(2): Displays information about robot operation and status.
  3. Action Icon: Definition lock() or release() state, play() or stop() state, crash() or safe()
    state.
  4. Power Consumption: Indicates the total power consumption in watts (W).
  5. System Version Information: System version information.